Electrical Energy Transmission
⑴Consider the situation shown in Figure1-1.
The rate of electrical energy flow (power ) from network A to network B
is
p=vi
Network A ---i, v---Network B
( Figure 1-1 Power transmission between two networks.)
⑵Lowercase letters are used to indicate instantaneous values,
that is, that p,v, and i may vary with time. High power levels require
high voltage and current values. For a given value of current, higher
power flows may be obtained by increasing the voltage, and vice versa.
Unfortunately, the existing technology sets practical upper limits on
allowable currents and voltages.
⑶What are the limiting factors for current? We fabricate power
conductors using materials with high conductivity, appropriate mechanical
characteristics, and that are economical: aluminum is the most common
choice, with copper used for some applications. The current-carrying capacity
of a conductor is related to its maximum allowable current density and
its cross-sectional area:
Imax= Jmax A
⑷The maximum current density Jmax is determined by the maximum
conductor temperature that will not damage the conductor or its insulation
system.
⑸What are the limiting factors on voltage? The fundamental
consideration is to provide electrical isolation (or insulation ) between
adjacent parts that can conduct current-that is, to confine current to
the paths through which it was intended to flow. When the voltage exceeds
the breakdown strength for a given insulation system, undesirable conduction
paths will be created and the system will be either temporarily or permanently
disabled. Fluid insulation tends to be "self-healing"(the system
will recover from a breakdown if it is de-energized for a short time and
then re-energized), whereas solid insulation is permanently damaged by
a breakdown.
⑹The meaning of "ground" is important I we quote
from the IEEE standard Dictionary of Electrical and Electronic Terms:
ground (earth ) (electric system). A conducting connection, whether Intentional
or accidental, by which an electric circuit or equipment is connected
to the earth, or to some conducting body of relatively large extent that
serves in place of the earth. Note: It is used for establishing and maintaining
the potential of the earth (or of the conducting body )or approximately
that potential, on conductors connected to it, and for conducting ground
current to and from the earth (or the conducting body).
We understand this to mean that at a given location in the power system,
accessible parts of power apparatus and earth constituted an equipotential
surface when perfectly grounded. Insulation of conductors' from ground
is a basic problem.
⑺Let us consider some different schemes for implementing the
transmission line indicated in Figure 3-1. For a fair comparison we select
constraints that all schemes must satisfy. We allow any number of conductors-
to be used, as long as each scheme uses the same amount of conducting
material. Given that networks A and B are separated by a fixed physical
length, this means that in viewing the lines in cross section we must
observe the same cross-sectional conducting area (A) for all schemes.
Also, we argue that no conductor shall carry current greater than that
constrained by some maximum current density Jo.
⑻We require that at least one conductor be grounded and shall
refer to such a conductor as the neutral, designated as "n. H If
it is not required to conduct any appreciable current, we will not include
its cross-sectional area in A. This condition is achieved under certain
symmetrical loading conditions, referred to as "balanced" loading,
and can be maintained in a practical situation 1 therefore we allow all
schemes to make this assumption. We require that for all schemes, no voltage
to ground exceed VO. It is assumed that the reader has a background in
basic circuit theory. The adjective "dc" essentially means time
invariant or constant with time. Recall that the term n ace, which historically
stood for "alternating current", in modern usage means "sinusoidal
steady state." These terms are used to describe voltages and currents
in time invariant (constant) steady-state and sinusoidal steady-state
modes.
|
|
电能的传输
⑴考虑 图 1-1 所显示出的状况。从网络A一联网B,电能流动的功率是:
p=vi
Network A ---i, v---Network B
(图 1-1:2 个网络之间的电能传播)
⑵其中,小写字母用来显示瞬时值, 即p、v ,并且i随时间变化。高功率要求高电压
和电流值。对于给定的电流值,高功率的能量流动可以通过增加电压获得, 反之也如此。
但是, 就目前存在的技术而言,实际中许可的电流和电压成了最高的限制。
⑶电流的限制因素是什么呢?我们通过使用具有高导电性、合适的机械特性的材料来制造输电导体,而且这些材料要求最经济:铝是最普通的选择,
在一些应用中铜也被使用了。导体的输电能力与它的最大电流密度和载面积有关:
Imax= Jmax A
⑷最大电流密度 Jmax 取决于不破坏导体(或者说不破坏导体的绝缘系统)的最大导体温度。
⑸电压的限制的因素是什么呢?首先要考虑的是相邻的传导电流的部分之间所能提供的隔离 (或屏蔽)作用,即, 限制电流传输到它预期流动的路径上。当电压超过确定绝缘系统的击穿值时,将出现预料之外的电流路径而且这个绝缘系统将暂时或永久地停止作用了。流体的屏蔽趋于是“
自我修复“ ( 如果短时间内释放能量,接着充满能量,系统将从故障中恢复过来), 但是固体的屏蔽却在故障中永久地损坏了。
⑹“ground”的内在含义是重要的,我们从 IEEE电气与电子校准术语词典中摘抄了如下内容:
地 ( 大地 )( 电力系统术语 ) 。一个传导性的连接, 无论是故意还是意外, 通过一个电路或设备被连结到地球上,或连结到可以代替地球的相对较大的导体上。注意:它是用来建立和维持地球的电势
( 或导体 ) 或近似的。大地电势是指,当有导体与之联接时,传导大地的电流到或者离开地球 ( 或取代地球的导电体 ) 。*译者注:任何一点的的电位通常都取作为零的大地导电体。
我们明白这意味着在电能系统中一个给定的位置, 当时,电能装置和大地的接近的部分组成了等势面如果是理想地面。导体与地面的屏蔽是一个基本问题。
⑺让我们为实现图 3-1 所示的电能传输考虑一些不同的方案。为了客观的比较,我们制定了各个方案必须满足的条件。我们允许任意数量的导体被使用,只要每个方案使用相同数量的导体材料。假设网络A和
B 被隔离为固定的物理长度, 这意味着在观察导线的载面时,我们一定能观察到相同的传导载面积(A)对于所有的方案。另外, 我们也认为没有导体能传导的电流大于由电流密度
Jo 所决定的限定值。
⑻我们要求至少有一个导体与地相接而且将其作为参考导体, 并将这个导体表示为“ n ”。 如果它没被要求传导任何预计的电流,我们在A中将不包括它的载面积。这个条件在一定的对称负荷条件下是可以实现的,
这涉及到“平衡”负荷,并且在一些实际状况中是能被维持的; 因此我们允许所有的方案做这个假设。我们要求所有的方案中没有一个接地电压能超过 VO
。在此假定读者对基本的电路理论已有一定的背景知识。形容词“ dc "在实质上表示时间是不变的或者随着时间变化而呈常态。记得术语“ac”,
它在历史上曾代表“交流电”, 而在现代意味着“稳定的正弦状态”。在不变的( 经常 ) 稳定状态和正弦稳定状态模式中,这些术语被用来描述电压和电流。
|